Product Overview
The MRI-4042 Analog interface module is designed to be used with a compatible fire alarm control unit, providing high rates of information exchange and fast and secure responses. The MRI-4042 Conventional Zone Module allows a zone of conventional two-wire detectors to be interfaced to an intelligent loop. It can also be configured to work with 4-20mA devices. An external listed power supply can be connected to several MIX- 4042 modules to provide power to the devices while remaining electrically isolated from the FACP. Each MRI-4042 monitors the current used by the devices and reports alarms and troubles accordingly. When configured for conventional devices, the module will automatically handle Class A or Class B lines. The MRI-4042 has an internal EOL resistor for Class A lines. An MP-300 end of line resistor must be used for Class B wiring. The module has a panel controlled LED indicator. The LED flashes during normal operation and stays ON steadily when the device is in alarm condition.
General Information
Name : Secutron MRI-4042 Conventional Zone Module , Secutron
Category : Control Panel Modules
UPC Code : 628090283211
Country of Origin : Canada. Country of origin is subject to change.
Specifications
General Information
ADI Part Number : 5T-MRI4042
Brand Name : Secutron
Manufacturer Part Number : MRI-4042